Skip to product information
1 of 2

Erie Controls VT3325 Zone Valve Body

Erie Controls VT3325 Zone Valve Body

Regular price $71.33 USD
Regular price Sale price $71.33 USD
Sale Sold out
Shipping calculated at checkout.

Low stock: 4 left

Quantity

SKU:33473

View full details

The VT3325 Zone Valve Body from Erie Controls is a robust 3-way valve designed for efficient heating and cooling applications. It features a 3/4 inch nominal size with threaded x threaded end connections, and a 2-position, spring-return actuator that provides a reliable normally closed, fail-safe operation.

Constructed with a forged brass body and a nickel-plated stem, it handles hot water and glycol with precision and enduring performance (flow 5 Cv). The unit is rated for 32–200°F fluids and up to 300 psi static with a 40 psi close-off rating. Horizontal or vertical mounting accommodates varying installation layouts, making it ideal for both new builds and retrofit projects.

Designed for longevity, the VT3325 incorporates a synchronous motor with hysteresis for long life and includes a manual override lever for maintenance or testing. This valve body is an excellent choice for reliable heating and cooling control in commercial and residential systems.

  • Type: 3-Way zone valve body
  • Nominal Size: 3/4 inch; End connections: Threaded x Threaded
  • Actuation: 2-Position, Spring Return; Normally Closed
  • Media: Hot/Chilled Water, Glycol; Flow: 5 Cv
  • Material: Forged Brass body; Stem: Nickel Plated; Paddle: Buna N
  • Operating: 32–200°F; Pressure: 40 psi close-off, 300 psi static
  • Mounting: Horizontal or Vertical

Specifications

Type3-Way
Pressure Rating40 PSI (Close-Off), 300 PSI (Static)
Temperature Rating32 to 200 Deg F (Fluid)
ApplicationHeating and Cooling
Body MaterialForged Brass
End ConnectionThreaded x Threaded
Mounting TypeHorizontal/Vertical
IncludesHysteresis Synchronous Motor for Long Life, Spring Return Operation Provides a Fail-Safe, Manual Override Lever
MediaHot/Chilled Water, Glycol
Actuation Type2-Position, Spring Return
Valve PositionNormally Closed
Valve Timing25 Second for 60 Hertz/30 Second for 50 Hertz/9 Second for Spring Return (Full Open to Full Close)