![Erie Controls VT3417 Zone Valve Body — New England Supply House spec card [NESH-SPEC-CARD-V2]](http://newenglandsupplyhouse.com/cdn/shop/files/spec-9032699216094.png?v=1782840844&width=1445)
Erie Controls VT3417 Zone Valve Body is a 1-inch, 3-way zone valve designed for precise control in heating and cooling systems. This valve features soldered x soldered end connections, a 2-position, spring-return actuator, and a normally closed configuration for reliable fail-safe operation. The forged brass body with a nickel-plated stem and Buna-N paddle seals delivers durable performance for hot water, chilled water, or glycol applications.
Designed for 24 VAC input (50/60 Hz), the VT3417 provides a robust flow capacity of 7.5 Cv and precise timing: 25 seconds at 60 Hz, 30 seconds at 50 Hz, or 9 seconds for spring-return full-open-to-full-close action. It supports heating and cooling applications with a wide temperature range (32–200 F) and strong pressure ratings (25 psi close-off, 300 psi static).
- 1-inch nominal size, 3-way valve with soldered x soldered end connections
- 2-position, spring-return actuation for reliable fail-safe operation
- Normally closed valve position
- Forged brass body with nickel-plated stem and Buna-N paddle
- Media compatibility: hot water, chilled water, glycol
- Flow capacity: 7.5 Cv; valve timing: 25 s (60 Hz) / 30 s (50 Hz); 9 s spring return
- Manual override lever for maintenance
- Hysteresis synchronous motor for long life
Specifications
| Type | 3-Way |
|---|---|
| Pressure Rating | 25 PSI (Close-Off), 300 PSI (Static) |
| Temperature Rating | 32 to 200 Deg F (Fluid) |
| Input Supply | 24 Volt AC at 50/60 Hertz |
| Application | Heating and Cooling |
| Body Material | Forged Brass |
| End Connection | Soldered x Soldered |
| Mounting Type | Horizontal/Vertical |
| Includes | Hysteresis Synchronous Motor for Long Life, Spring Return Operation Provides a Fail-Safe, Manual Override Lever |
| Media | Hot/Chilled Water, Glycol |
| Actuation Type | 2-Position, Spring Return |
| Valve Position | Normally Closed |
| Valve Timing | 25 Second for 60 Hertz/30 Second for 50 Hertz/9 Second for Spring Return (Full Open to Full Close) |