Carlin 60200FRS Oil Burner Primary Control provides reliable flame establishing control for oil burner systems. The Carlin 60200FRS Oil Burner Primary Control features a 15-second flame establishing period and a pilot-type interrupted ignition to promote safety and efficiency.
This primary control is designed for 120 Volt AC at 60 Hz operation and is UL approved for both Canada and the United States. It supports an operating temperature range from 32 to 140 Deg F and mounts in a 4x4 inch junction box, making it a compact and robust solution for oil burner applications.
- Voltage & power: 120 VAC, 60 Hz; Power Rating 9 Volt-Amp; Motor Load 10 A (Full Load) / 60 A (Locked Rotor).
- Ignition & flame: Pilot type interrupted; Flame establishing period of 15 seconds; Igniter Load 120 VAC, 60 Hz, 500 VA.
- Valve & alarms: Valve Load 2 A; Alarm Contact Rating 24 VAC/DC, 2 A; Thermostat anticipator current 0.1 A.
- Mounting & compatibility: 4 inch x 4 inch junction box mounting; UL listed for Canada and US.
Specifications
| Voltage Rating | 120 Volt AC at 60 Hertz |
|---|---|
| Application | Oil Burner |
| Approvals | UL (Canada and US) |
| Operating Temperature | 32 to 140 Deg F |
| Flame Establishing Period | 15 Second |
| Pilot Type | Interrupted |