![Honeywell Commercial T775R2027 Electronic Remote Temperature Controller — New England Supply House spec card [NESH-SPEC-CARD-V2]](http://newenglandsupplyhouse.com/cdn/shop/files/spec-9032792146142.png?v=1782843590&width=1445)
Honeywell T775R2027 Electronic Remote Temperature Controller is a standalone remote temperature controller designed for heating, cooling, boiler, and chiller applications. This compact device uses a 1/4 inch diameter x 2 inch length bulb and comes with two sensors, delivering precise control in a rugged NEMA 1 enclosure.
The controller supports wide operating ranges and flexible setup. Temperature range is -40 to 125°F at 50 Hz and -40 to 140°F at 60 Hz, with a set point range from -40 to 248°F and a differential of 1 to 150°F, ensuring accurate response to process changes. It features a relay output with reset and two SPDT contacts for reliable switching across various loads.
- Output: Relay with Reset
- Contacts: 2 SPDT
- Connection: Conduit
- Enclosure: NEMA 1
- Sensors: 2 inputs; includes two 50021579-001 sensors
- Sensor element: 1097 Ohm PTC at 77°F
- Max sensor distance: up to 1000 feet
- Approval: UL (US/Canada), CUL, CE, C-Tick
- Applications: Heating, Cooling, Boiler, Chiller
- Dimensions: 4-13/32 W x 2-15/16 D x 8-5/32 H inches
Trusted Honeywell quality with robust electrical ratings (various loads up to 1/2 HP at 120/240 V) and wide compatibility make the T775R2027 a versatile choice for precise temperature control in demanding commercial environments.
Specifications
| Type | 1/4 Inch Diameter x 2 Inch Length Bulb, Standalone |
|---|---|
| Application | Heating, Cooling, Boiler, Chiller |
| Approvals | UL (Canada and US), CUL, CE, C-Tick |
| Enclosure | NEMA 1 |
| Contact Configuration | (2) SPDT |
| Contact Rating | 10 Amp at 24 Volt AC (Resistive), 9.8 Amp at 120 Volt AC/4.9 Amp at 240 Volt AC (Full Load), 58.8 Amp at 120 Volt AC/29.4 Amp at 240 Volt AC (Locked Rotor), 125 Volt Amp at 120/240 Volt AC (Pilot Duty), 1/2 HP at 120/240 Volt AC |
| Temperature Range | -40 to 125 Deg F at 50 Hertz, -40 to 140 Deg F at 60 Hertz |
| Connection Type | Conduit |