![Honeywell Thermal Solutions FSG RM7890A1056 Burner Control — New England Supply House spec card [NESH-SPEC-CARD-V2]](http://newenglandsupplyhouse.com/cdn/shop/files/spec-9032814624990.png?v=1782844100&width=1445)
The FSG RM7890A1056 Burner Control by Honeywell Thermal Solutions is a microprocessor-based, integrated control that delivers precise flame establishment, fast startup, and dependable safety for single-burner systems. It is ideal for on-off primary control with automatically fired gas, oil, or a combination fuel, offering robust sequencing, fault detection, and easy field diagnostics.
Designed for reliability in harsh environments, this 120 V AC control fits a compact 5 x 5-1/4 x 5 in enclosure and supports a pilot-type intermittent cycle. The flame establishment period is 4/10 second for the pilot, followed by the intermittent main flame, delivering precise sequencing and safe startup. The unit operates across -40 to 140 F during shipping and storage and carries UL, CSA, FCC, SRE, and FM approvals, enabling straightforward integration into single-burner gas, oil, or combination systems.
- Automatic burner sequencing
- Flame supervision and system status indication
- Self-diagnostic and trouble shooting
- Pre-ignition for safe startup
- Intermittent pilot and main flame establishment
- UL/CSA/FCC/SRE/FM approvals
Specifications
| Type | Microprocessor Based, Integrated |
|---|---|
| Size | 5 Inch Width x 5-1/4 Inch Depth x 5 Inch Height |
| Voltage Rating | 120 Volt AC at 50/60 Hertz |
| Application | On-Off Primary Control, Automatically Fired Gas/Oil/Combination Fuel Single Burner |
| Approvals | UL, CSA, FCC, SRE, FM |
| Flame Establishing Period | 4/10 Second (Pilot), Intermittent (Main) |
| Pilot Type | Intermittent |